Automatic restart of loads after UPS shutdownAutomatically starts up the connected equipment upon the return of utility power.Automatic self-testPeriodic battery self-test ensures early detection of a battery that needs to be replaced.Battery failure notificationProvides early-warning fault analysis on batteries enabling timely preventive maintenanceECO ModeOperating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protectionLCD Status DisplayProvides key UPS status at a glance. Multiple status indicators with load and battery bar graphs.Cold-start capableProvides temporary battery power when the utility power is out.Safety-agency approvedEnsures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.Resettable circuit breakerEasy recovery from overloads; no need to replace a fuse. (Not available on Wall Tap SKUs)Power conditioningProtects connected loads from surges, spikes, lightning, and other power disturbances.Input Power Factor CorrectionMinimizes installation costs by enabling the use of smaller generators and cabling.Generator compatibleEnsures clean, uninterrupted power to protected equipment when generator power is used.Frequency and voltage regulationGives higher application availability by correcting poor frequency and voltage conditions without using the battery.SmartSlotCustomize UPS capabilities with management cards.Network manageableMost models provide remote power management options of the UPS over the network. Many do not have NMC embedded.Serial connectivityProvides management of the UPS via a serial port.InfraStruXure Manager CompatibleEnables centralized management via the APC InfraStruXure Manager.LED status indicatorsQuickly understand unit and power status with visual indicators.
Features | |
UPS topology: | Double-conversion (Online) |
Output power capacity: | 6 kVA |
Output power: | 6000 W |
Waveform: | Sine |
Input operation voltage (min): | 100 V |
Input operation voltage (max): | 285 V |
Input frequency: | 40/70 Hz |
Output operation voltage (min): | 220 V |
Output operation voltage (max): | 240 V |
Output frequency: | 50/60 Hz |
Surge energy rating: | 600 J |
Crest factor: | 3:1 |
ECO mode: | |
Emergency Power Off (EPO): | |
Output voltage Total Harmonic Distortion (THD): | 2% |
Noise level: | 55 dB |
Audible alarm(s): | |
Audible alarm modes: | Alarm when on battery, Low battery alarm, Overload alarm |
Ports & interfaces | |
AC outlet types: | C13 coupler, C19 coupler |
AC outlets quantity: | 3 AC outlet(s) |
USB port: | |
Serial interface: | |
Ethernet LAN (RJ-45) ports: | 1 |
Emergency Power Off (EPO) connector: | |
SmartSlot: | |
Battery | |
Battery technology: | Sealed Lead Acid (VRLA) |
Battery voltage: | 96 V |
Battery life (max): | 5 year(s) |
Battery recharge time: | 4 h |
Hot-swap battery: | |
Automatic battery test: | |
Cold start: | |
Design | |
Form factor: | Compact |
Product colour: | Black |
Display type: | LCD |
LED indicators: | |
International Protection (IP) code: | IP20 |
Certification: | CE, EN/IEC 62040-1 |
Operational conditions | |
Operating temperature (T-T): | 0 - 40 °C |
Storage temperature (T-T): | -15 - 45 °C |
Operating relative humidity (H-H): | 0 - 95% |
Storage relative humidity (H-H): | 0 - 95% |
Operating altitude: | 0 - 2011 m |
Non-operating altitude: | 0 - 15240 m |
Weight & dimensions | |
Width: | 440 mm |
Depth: | 620 mm |
Height: | 178 mm |
Weight: | 51.9 kg |
Package width: | 590 mm |
Package depth: | 790 mm |
Package height: | 275 mm |
Package weight: | 59 kg |